Q: We are using GSK218MC CNC controller to retrofit our machine, now all the connection are done, but the external MPG is not working, is there any parameter should be changed?
A: The default parameter of GSK218MC is set for MPG on panel, if you are using the external MPG like ZSSY1468-001-100B-5L, please set GSK218MC K parameter No.5.0 as 1, and if there is no emergency stop on the external MPG, you might need to set K parameter No.7.5 as 1 to disable the emergency alarm.
|