GD2000 AC Servo Driver Error

 

GD2000 AC Servo Driver User:

Dear CNCmakers, We are testing now . But all the drive alarm error 13 . WE THINK IT MAY CAUSED FROM SOME PARA DOES NOT MATCH , could you pls introduce para list that should to be set at drive unit to match the motor model

If we try one by one is so terrible and fall in too much time therefore we need your para list that match between motor & drive

 

CNCmakers Support:

Dear, please refer to below http://www.cncmakers.com/cnc/Tech_Support/AC_servo_driver_Err13_alarm.html

 

GD2000 AC Servo Driver User:

Dear CNCmakers , After we check we try many time to revisable of parameter follow the manual but it is very task and difficult. We think that the manufacturer may not set the right para for us. Could you pls let me have para list of servo drive suitable value with motor model ?

We try from morning until now .It is still have error and some time noise of motor. We do not think the motor or drive fault but para setting is problem . But for us it take to long time to test & adjust to the right value match together. But the manufacturer side must have. Kindly let us have the list by soon.

Yes, need to adjust but even we try only without load test it does not work. Always alarm occurred . Therefore we think the maufacturer set the para not correct .they should have their test result that drive unit with thid motor unit value that most power working. Or you may introduce which para we can try to adjust and the value should be try. TO DROP ALARM Error -13.

The CNCmakers must have their record testing that prove the GD 2000 can be used with 175SJT M300D without problem.

 

CNCmakers Support:

The parameter of the driver and motor has been set before shipment

Have you checked the input voltage?

 

GD2000 AC Servo Driver User:

In previous you send us GS 2000 with motor we not need to set any thing just plug in .It can be used

We received GD 2000 Pa 1 they set 63  it is not correct model noise occurred  but we check the manual it should be 66 we replace it 66 also have noise and alarm cut off . INPUT VOLTAGE 220 /210

How can be 3 units the same result. Now we are doing test the 4th unit that we want to keep spare. TO CONNECT OUT SIDE MACHINE WITHOUT LOAD WEATHER IT WORK OR NOT. IF YOU HAVE THE PARA TEST LIST THAT THE RIGHT ONE .KINDLY SEND TO US IMMEDIATELY TO DROP OUR TIME DELAY AND FALL IN TOO MUCH SPEND TIME ON TROUBLE SHOOTING UNNECCESARY.

 

CNCmakers Support:

Sometime the lack of phase will cause the 13 alarm, please kindly Check the UVW input, are the 3 phases input power connected well?

 

GD2000 AC Servo Driver User:

Caused from Pa 1 settinv is wrong not match therefore it may not correct para setting from factory therefore I need to check their para list refferencd testing value.

 

CNCmakers Support:

After you changed the PA1, then you need to restore the driver, all the parameter will be changed to match the motor automatically

Have you restored the drivers?

 

GD2000 AC Servo Driver User:

We follow the book instruction thank you

Yes we are wrong the engineer error. AFTER I GO DOWN STAIR SEE HE SET IT IS OK WE RESTORED THE DEFAULT , Thank a lot.

 good drive & motor