GS3000Y AC Servo Spindle User: I have a question for you, regarding Spindel Drive GS 3000,
On plug CN 1, connector 40, SRDY, servo ready output, i have always 0 V, even by hawing a alarm. Do i have to set the signal in a Parameter ?
Also i would like to check if spindel is rotating or not rotating, would this be on plug CN1, connector 42, ZSP ? On connector 42, i have always 24 V. Do i have to set the function in a Parameter ?
CNCmakers Support:
There will be always output for SRDY, as long as there is no alarm, and there is no parameter to set it. ZSP can be set by PA62.
|